| S/No |
Service |
Designation |
Specification/ Proposal |
| 1 |
Building |
Data centre floor space |
2000-3000m2 contiguous floor space seperated into 3 distinct rooms |
| 2 |
Building |
Structure floor loading |
12kPA |
| 3 |
Building |
Clear ceiling height |
4.0M |
| 4 |
Utility Supply |
Incoming HV feeds |
Dual redundant source A+B (2N) |
| 5 |
Utility Supply |
Transformers |
2N |
| 6 |
Electrical |
Emergency power generator |
2N |
| 7 |
Electrical |
UPS system configuration |
2N |
| 8 |
Electrical |
UPS battery autonomy |
15 minutes autonomy at load |
| 9 |
Electrical |
Final circuits to cabinets |
2N (32A circuits) including branch circuit monitoring |
| 10 |
Electrical |
DC power system |
2N (2000A, -48V) 4hrs of autonomy at full load |
| 11 |
Electrical |
Cabinet requirements |
500-600 cabinets (600x1200x2200) |
| 12 |
Electrical |
Power capacity for cabinets |
4.5 kVA average (Maximum of 12 kVA) |
| 13 |
Mechanical |
Cooling (CRAC) units |
N+1 unit redundancy |
| 14 |
Mechanical |
Heat rejection (Chiller) units |
N+1 unit redundancy |
| 15 |
Mechanical |
Cooling reticulation |
Ring perimeter served from dual risers. No single point of failure. |
| 16 |
Mechanical |
Fluid leak detection |
To all Colocate cabinet areas along pipe work routes |
| 17 |
Fire Protection |
Alarm and detection |
Convential and VESDA |
| 18 |
Fire Protection |
Suppression |
Pre-action sprinkler (offices). Gas suppression (cabinet area). |
| 19 |
Security |
Intruder detection |
CCure 800+ system (Chubb) to comply with local regulations |
| 20 |
Security |
CCTV |
All entrances and exits, all cabinet aisles, external areas. |
| 21 |
Security |
Access control |
All entrances and exits |
| 22 |
BMS/ FM |
Building management system |
Monitoring and control of all E&M services |
| 23 |
Telecom |
Telecom riser |
Dual access and dual risers for major local carriers |